Oxygen Scavengers
If left untreated, boiler water derived oxygen will corrode metallic boiler components leading to increased maintenance costs and reduced boiler efficiency.
See ProductsAccepta’s technically advanced boiler water treatment chemicals have been scientifically formulated to improve the operation and maintenance of industrial boiler systems and steam generation plants
Boiler water treatment; Industrial boilers and steam raising plant are used extensively in many commercial, manufacturing and industrial processes.
To ensure that such boiler systems are correctly maintained and operate at optimum efficiency it is essential that the correct boiler water conditions are maintained at all times. This can be achieved dosing selected boiler water treatment chemicals into the feed water.
If you are a water treatment specialist, FM or maintenance company who regularly resells water treatment products to your customers why not apply to become an Accepta Registered Reseller.
Accepta’s technically advanced boiler water treatment chemicals have been scientifically formulated to improve the operation and maintenance of industrial boiler systems and steam generation plant by proactively managing the problems associated with the use of water including scale formation, metallic corrosion, boiler water carryover and sludge deposition.
If left untreated, boiler water derived oxygen will corrode metallic boiler components leading to increased maintenance costs and reduced boiler efficiency.
See ProductsTo ensure that such steam boiler systems are well maintained and operate at optimum efficiency it is essential that the correct water conditions are maintained at all times.
See ProductsTo ensure that such steam boiler systems are well maintained and operate at optimum efficiency it is essential that the correct water conditions are maintained at all times.
See ProductsThe formation of deposits of scale or baked on suspended solids will reduce efficiency and may make the boiler unsafe to operate.
See ProductsThe control of boiler water pH and alkalinity levels are important issue affecting the operation and maintenance of industrial boiler systems and steam raising plant.
See ProductsComplete as much of this form as possible to get your bespoke boiler chemical dosage treatment recommendations.
Acid descaling and neutralising products suitable for boiler descales & other descaling applications.
Blend of surface active agents for control of foam in steam boilers and high temperature applications
Ensuring you are using the best boiler water chemicals for your application is very important as using the wrong chemicals can be much more costly in the long run and may not provide adequate treatment for your steam boiler.
Different operating pressures, system materials and make-up water chemistry have an impact on the treatment program your industrial boiler should be on. To assist in making the right choice Accepta have provided guides within each treatment category to make selection easier, you just need to know where to start.
A Steam Boiler treatment program should always include an oxygen scavenger and polymer treatment. It is typical to also include a phosphate treatment especially in applications above 10 bar (150 psi). While it is always necessary to control the alkalinity, where the makeup water is reliably softened the regular use of an alkalinity builder may not be necessary.
The above is general guidance and advises beginning with an Oxygen Scavenger and Polymer Scale Inhibitor Treatment, these can be found separately in the categories above however they can also be supplied in a blended multi-functional treatment based on Tannin or Sulphite which suit most applications. Carbohydrazide or DEHA treatments can be found in Oxygen Scavengers.
Next, you need to decide whether you require a Phosphate Supplement in your boiler program, this comes down to pressure and natural alkalinity in the make-up water and is highly recommended in the following situations:
Combined with Polymers, Phosphate will precipitate calcium and magnesium hardness from the boiler water into a sludge which is ejected during blowdown.
If you require any advice on treatment and recommended programs for your industrial steam boiler please contact us today.
pH
10 minimum
Caustic Alkalinity (Alk OH)
mg/l as CaCO3
350 minimum
Total Alkalinity (Alk M)
mg/l as CaCO3
1200 maximum
Total Hardness
mg/l as CaCO3
Less than 10
Sulphite Reserve or Tannin
mg/l as Na2SO3 or Tannin units
50-100 or 12-20
Total Dissolved Solids
mg/l
3000 maximum
Silica
mg/l as Si O2
Less than 40% of Caustic Alk
Phosphate
mg/l as PO4
30-70
Suspended Solids
Light