Description
Kintec 2198 is a high performance, FDA compliant boiler water oxygen scavenger formulated using a blend of natural organic compounds which offer both corrosion inhibition and dispersive properties.
Corrosion inhibition is achieved via the dual ability of the selected compounds within Kintec 2198 to act as an oxygen scavenger plus the supportive benefit of forming a protective film on the metal surface.
Kintec 2198 can also aid in magnetite film formation in the boiler.
Kintec 2198 is a short shelf-life product as it does not contain any preservative.
Product Benefits
- High-performance oxygen scavenger giving outstanding protection from oxygen corrosion
- Excellent corrosion inhibition and dispersive properties
- Aids in magnetite film formation in the boiler
- Convenient liquid product
- FDA compliant boiler treatment
Product Properties
Form: | Liquid |
Colour: | Dark brown |
Specific Gravity: | 1.07 – 1.12 |
pH: | 5.0 – 6.0 |
*Full details of the product properties are available in the Safety Data Sheet. See below.
Application & Dosage Information
The target dosage range for Kintec 2198 is 55ppm of product/ppm of 02 with a residual level of 400 – 600 ppm in the boiler water.
Recommended dosage ranges are compliant and within the FDA requirements.
Dosage Strategy
Kintec 2198 should be diluted no more than twenty times using softened or demineralised water (or condensate) and is dosed using either a metering pump (preferred) or a pot feeder, as appropriate.
Kintec 2198 is normally controlled within set limits in the boiler water. The specific limits will be determined by operating conditions and water quality.
Performance Monitoring
Appropriate use of Kintec 2198 following the above dosing strategy will result in oxygen removal in the boiler water. use.
Testing and Control
Kintec 2198 – Test using tannin, colourimetric or pocket colourimeter both available from Accepta.
Material of Compatibility
Material | Comment |
SS : | Acceptable |
MS : | Acceptable |
PE : | Recommended |
PP : | Recommended |
PVC : | Recommended |
Teflon : | Recommended |
Safety, Storage & Handling
Kintec 2198 is a mildly acidic solution. Avoid contact with skin, eyes or clothing. If skin comes into contact with this product, wash with water. If eyes are affected, flush with water for at least 15 minutes and get medical attention.
For full details concerning safety precautions, storage and handling procedures for this product please refer to the latest Safety Data Sheet.
To request the latest MSDS for this product please fill out the form below.