Description
Kintec 3305 is a high performance nitrite and organic corrosion inhibitor developed for use in the treatment and protection of closed loop systems that do not contain aluminium.
NOTE: Do NOT use in systems containing aluminium.
Product Benefits
- High performance corrosion inhibitor for closed loop systems
- Nitrite / organic formulation
- Convenient liquid product
Product Properties
Form: | Liquid |
Colour: | Clear, brown |
pH: | 11.0 – 13.0 |
Specific Gravity: | 1.10 – 1.20 |
*Full details of the product properties are available in the Safety Data Sheet. See below.
Application & Dosage Information
Target dosage range for Kintec 3302 is 500 – 1,000 ppm as NaNO2 in the closed loop system.
Dosage Strategy
Kintec 3305 should be fed neat using a chemical metering pump or via a bypass pot feeder to a system location where it can be uniformly distributed.
Avoid thorough mixing or prolonged contact with air.
Performance Monitoring
Appropriate use of Kintec 3305 following the above dosing strategy should result in a corrosion rate of less than 1 mpy.
It is always advisable to carry out a ‘Control Of Substances Hazardous to Health’ (COSHH) assessment before use.
For additional assistance please contact Accepta.
Test Methods
- Nitrite Drop test
- Nitrite Colour Disc
Material of Compatibility
Material | Comments |
SS : | Recommended |
MS : | Recommended |
PE : | Recommended |
PP : | Recommended |
PVC : | Not recommended |
Teflon : | Acceptable |
Safety, Storage & Handling