Description
Kintec 3302 is a high performance cooling water corrosion inhibitor developed for the treatment and protection of closed loops.
Kintec 3302 is scientifically formulated from a blend of inorganic and organic corrosion inhibitors for use in closed loop systems.
Kintec 3302 is designed for use in low/medium pressure hot water systems, and in particular those containing aluminium.
Product Benefits
- High performance corrosion inhibitor for closed loop systems
- Ideal for high low/medium pressure hot water systems
- Ideal for systems containing aluminium
- Convenient liquid product
Product Properties
Form: | Liquid |
Colour: | Clear, light brown |
pH: | 8.0 – 8.6 |
Specific Gravity: | 1.10 – 1.20 |
Freezing Point: | 10°C (14°F) |
*Full details of the product properties are available in the Safety Data Sheet. See below.
Application & Dosage Information
Target dosage range for Accepta 2620 is 165 – 220ppm as Mo in the closed loop water.
Dosage Strategy
Kintec 3302 should be fed neat using a chemical metering pump or via a bypass pot feeder to a system location where it can be uniformly mixed and thoroughly distributed.
Performance Monitoring
Appropriate use of Accepta 2620 following the above dosing strategy should result in a corrosion rate of less than 2 mpy.
It is always advisable to carry out a ‘Control Of Substances Hazardous to Health’ (COSHH) assessment before use.
For additional assistance please contact Accepta.
Test Methods
- Molybdate Checkit kit (comparator)
- Molybdate Colour Disc
Material of Compatibility
Material | Comments |
SS : | Recommended |
MS : | Recommended |
PE : | Recommended |
PP : | Recommended |
PVC : | Not recommended |