Description
Accepta 2534 is a very high performance, premium strength nitrite based water treatment corrosion inhibitor, scientifically formulated for the protection of closed circuits, low and medium pressure hot water systems and chilled water systems.
Offering superior results Accepta 2534 is our premium strength nitrite based formulation which includes phosphonate, polymer and azole to offer the ideal, economical choice of corrosion control for steel, cast iron, brass and copper.
IMPORTANT – Accepta 2534 is not suitable for systems containing aluminium.
Product Benefits
- High performance, premium strength nitrite corrosion inhibitor
- Suitable for closed circuit, low and medium pressure hot water systems
- Suitable for chilled water systems.
- High strength nitrite based product
- Excellent corrosion control for steel, cast iron, brass and copper.
- Economical
Product Properties
Fprm: | Solution |
Colour: | Pale straw |
Odour: | Slight |
pH: | >10 |
Specific gravity: | 1.33 |
Solubility in water: | Completely miscible |
Decomposition temp: | Decomposes at boiling point |
*Full details of the product properties are available in the Safety Data Sheet. See below.
Application & Dosage Information
Generally Accepta 2534 should be dosed to give 0.25% product in the system. This gives 1000 ppm sodium nitrite in the system.
The system should be clean when dosed.
Please note that Accepta 2534 will mobilise corrosion debris.
Dose an isothiazolinone based closed circuit corrosion inhibitor.
Do not mix Accepta 2534 with other chemicals unless advised by your Accepta consultant.
It is important to monitor the product concentration, pH and microbiological status regularly.
NOTE – Accepta 2534 is not suitable for systems containing aluminium.
Testing & Control
Measure nitrite using an Accepta nitrite drop test kit.
It is always advisable to carry out a ‘Control Of Substances Hazardous to Health’ (COSHH) assessment before use.
For further technical assistance concerning Accepta 2534 please contact Accepta.